Models and versions
BT510; BT520; BT520ANG; BT521; BT521ANG
Resistance ranges and resolution
3 mΩ → 0.001 mΩ; 30 mΩ → 0.01 mΩ; 300 mΩ → 0.1 mΩ; 3000 mΩ → 1 mΩ
Resistance measurement method
4-wire; AC injection <100 mA, 1 kHz; DUT ≤60 V
R accuracy with standard probes
3 mΩ: ±(1% + 8 counts); other ranges ±(0.8% + 6 counts)
R accuracy with ANG probes
3 mΩ: ±(1% + 68); 30 mΩ: ±(0.8% + 12); 300/3000 mΩ: ±(0.8% + 6 counts)
DC voltage ranges
BT510/BT520/BT520ANG: 6 / 60 / 600 V; BT521/BT521ANG: 6 / 60 / 600 / 1000 V
DC voltage accuracy
±(0.09% + 5 counts)
AC voltage
600 V, 45…500 Hz; 0.1 V; ±(2% + 10 counts)
Frequency
≤500 Hz; 0.1 Hz; ±(0.5% + 8 counts)
Ripple voltage
600 / 6000 mV; 0.1 / 1 mV; ≤20 kHz
BT521 current measurement
With i410: 400 A AC/DC; 1 A; ±(3.5% + 2 counts)
BT521 temperature measurement
With straight BTL21 probe: 0…60 °C; 1 °C; ±2 °C
ANG probes
BTL20ANG; 20° tip angle; no temperature sensor
Meter mode memory
999 records per measurement position, time stamp
Sequence mode memory
100 profiles and 100 templates; up to 450 batteries per profile
Thresholds
Up to 10 sets; PASS/WARN/FAIL
Wireless communication
BT521: Battery Analyze mobile app; not Fluke Connect compatible
Computer interface
Mini-USB; Fluke Battery Management Software
Power supply
BP500 Li-ion; 7.4 V, 3000 mAh; >8 h
Protection and electrical category
IP40; CAT III 600 V
Operating temperature
0…+40 °C
Dimensions and weight
220 × 103 × 58 mm; 850 g
Standard probe differences
BT510: BTL10; BT520: BTL10 + BTL20; BT521: BTL10 + BTL21 + i410
Common package
Instrument, leads, battery/charger, USB cable, straps, software and case; according to version
Base-model part numbers
BT510: 4489970; BT520: 4489981; BT521: 4489996